EDITORIAL

October 2016 (UPDATED April 7th, 2017)
 

Spotting A Rogue Verifier

“You can put wings on a pig, but you don't make it an eagle.”
-- William J. Clinton

“Hide nothing, for time, which sees all and hears all, exposes all.”
-- Sophocles

By Frank Kurz

DISCLAIMER!  I made a very specific promise several years ago, and I intend to stick by it, so this is NOT the resurrection of the  Burning Brick Awards some may have been expecting (please try to control your disappointment).  This article won’t mention the name of the individual and replaces the name of the company involved with Trunk Slammer Safety, Inc., a purely fictitious, but eminently appropriate invention of the writer.  The intent of this editorial is to both INFORM AHJ’s in Canada and WARN building owners, the engineering and contracting communities, that the fire alarm Verification documentation you receive might not be worth the paper it’s printed on.

Our new series provides an insightful, in depth analysis on the Fire Alarm Verification process and affords  jurisdictional authorities with some basic information about what you should expect to see in the way of documentation!

Anytown, Canada - The building that is the subject of this particular story is located right on AnyTown’s main drag (aptly named AnyTown Street).  In 2012, the outdated EPEL fire alarm control equipment was replaced by a Mircom FX-2000 system supplied and Verified by a supposedly qualified individual (Trunk Slammer Safety, Inc. maintains branch offices in every city across Canada).  I had been given to understand that the bid process for the panel replacement was lengthy and quite convoluted, with a number of service providers participating.  When the contract was finally awarded, the winning bid came in at considerable savings over the others that were tendered, and the work of replacing the old system began.

Now, keep in mind that the EPEL system is a conventionally zoned fire alarm panel which employs conventional field devices (heat detectors, smoke detectors, bells, and manual stations).  The Mircom FX-2000, with which it was replaced, is a fully addressable system that employs four (4) conventional signalling circuits on the main common control board and a single data loop controller.  This means that you must employ a combination of active field devices (like fully addressable smoke and heat detectors, and manual stations) and supporting field devices to enable it to interface with conventional smoke and heat detectors as well as other field devices like sprinkler valve tamper and flow switches.  The Mircom FX-2000 can support a wide array of optional field addressable input zone and output modules (the aforementioned supporting field devices).  These include:

MIX-501P - Is a “mini” module designed to fit into a single gang (or other approved for installation) back-box for connection to contact type devices like manual stations, heat detectors, low temperature sensors and the like.

MIX-501MAP - Is a single zone interface module designed to mount on a 4x4 box.  It’s used to connect a variety of contact type field devices as well (like heat detectors, flow switches, manual stations, etc.).

MIX-502MAP - Is a single zone module designed to support conventionally wired smoke detectors.  The main difference between it and the previous modules we mentioned is that it also requires a 24VDC power source connected to it (to power conventional two-wire smoke detectors).  Of course, you can also connect contact type devices to it.

MIX-500X - This is an Data Communication Link isolator module.  It protects the DCL (Mircom’s manual identifies it as “SLC”) loop from shorts.  There’s an extensive article into its required use (including the various Standards referenced) in this special report.

What made this particular installation troubling is something the servicing agency which performed a recent test on the system mentioned to me, while we were engaged in discussing the topic of performance testing (to CAN/ULC-S536) addressable fire alarm systems.  Not only did several smoke detectors fail to respond to test smoke, when two conventional heat detectors where physically tested, a communication fault appeared on the system and all programmed devices on the respective DCL loop suddenly went missing.  On further investigation it was determined that there were NO supporting field devices installed for either of these two detectors!  With so many glaring errors already identified, it was at this time that I suggested we should review the Verification Appendix “C” report that must have been filed for the installation.

In accordance with the above disclaimer I won’t reveal the NAME of the service company involved, nor will I provide information regarding the physical location of the building.  I am providing you the report in its entirety (with this information redacted), so you can better understand the subject of this editorial and gain some insight into how one particular agency decided to document one of the most crucial tests a fire alarm system must ever undergo in, what I’m certain, are many similarly completed projects (some perhaps even in YOUR jurisdiction).  The missing sections and information will be made clear when we detail the deficiencies afterwards.  It’s important for anyone reviewing a fire alarm system Verification Appendix “C” Report to understand that, while the sample format ULC suggests is an Appendix Item (the Appendix of any Standard is informative and not prescriptive), the body of the Standard makes reference to its use by employing the word “shall”, and subtle variations of this phrase: “similar to that shown in Appendix C, Fire Alarm System Verification Records” in almost every requirement in Section 3.2 Documentation of CAN/ULC-S537-04 and Section 4.2 Documentation of CAN/ULC-S537-13.

Bogus CAN/ULC-S537-04 Fire Alarm Verification Appendix "C" posted by Frank Kurz on Scribd

 

 

panel_tl

panel_tr

Canadian Building Life Safety Systems Training Initiative:
Advance
Accelerate
Achieve

Visit our Training Centre!
 

Certification Programme:
Vigilance
Knowledge
Integrity

Professional Certification of building Life Safety Systems Technologists and Specialists in Canada
 

 

Technical Forums:
Friendly reminder! The Forums are alive!
 

Questions?
Please contact us
by calling the number above or by clicking the email link!
 

 

Common Fire Alarm Trouble Signals:
We're compiling a list of common fire alarm trouble signals and displays HERE!
 

FAQ’s:
Access the most extensive fire protection equipment and service FAQ on the planet!
 

Forms:
We've updated the Fire Alarm Inspection and testing forms in our library (July, 2014).
Check out the latest version on our Forms page!
 

 

In Memoriam
G. Richard (Rich) Morris
Celebrating a truly
remarkable life!

CFAA’s Tribute
SCC’s Tribute

In Memoriam
David Sylvester
CFAA Legend, Educator,
and Friend!

CFAA’s Tribute

 

 

Smoke Detector Cross Listing Information:
ULC Smoke Detector Compatibility Index
(You’ll be prompted to either “save as” or “open” a Microsoft a Microsoft® Excel document. Please read our Terms of Use.)

 


If you've found our site useful, you may wish to consider supporting our efforts by becoming an Associate Member.

 

panel_bl

panel_br


Mircom FX-2000 Fire Alarm Control
Verification Label

When you simply replace a conventionally wired control panel (without any upgrades or modifications to the field wiring or devices), it’s pretty well a given that you have to make the new system work the same way the original was designed, unless  the local jurisdictional authority insists that the system be updated to current Building Code and CAN/ULC-S524 requirements.  At the very least, when you’re upgrading to an addressable system you are required (without exception) to employ isolators within the various floor areas in order to ensure the entire system isn’t compromised by a single “short circuit” fault (you can also achieve the required level of performance by employing separate loop controllers for each area).  As a matter of fact, the Installation Standard is very clear on this (reference the Clauses which are provided in the aforementioned article).  Since there are NO ISOLATORS installed in the referenced system (and none mentioned on the Verification Appendix “C” report), if you impose a short across any of the data loops (which a conventional heat detector wired directly to one would do when activated), you will essentially take down the loop controller and all the devices associated with it.  In a worst case scenario, if your system employs only one such controller (a single addressable loop), you’re essentially rendering the entire fire alarm system non-functional

When you add to this the failure to mention any pertinent information relating to all of the installed supporting field devices (the addressable modules that are a part of this system), and the absence of the documentation actually required by the Standard which is supposed to support a properly conducted Fire Alarm Verification, you have a Life Safety System with highly questionable performance even in the best of conditions.  I shudder to think what’s going to happen during an actual fire emergency when occupant notification becomes even more critical and an absolute necessity.

I am going to outline all of the deficiencies I identified in a brief site visit I made and my examination of the pertinent documentation:

    1.  The fire alarm Verification report does NOT comply with the acceptable format for a CAN/ULC-S537-04 Appendix “C” required by NBC 2005 (BCBC 2006).  The form employed in this instance utilizes a Vancouver version Appendix “C1” first page and incorporates five (5) attached individual device test record sheets (the subject system documented by this bogus Verification is located in the eastern part of British Columbia).  The referenced Standard details the minimum acceptable Appendix “C” report in Clauses 3.2.1 through 3.2.7, which must consist of Sections “C1” through “C6.3” as follows:

      C1.  FIRE ALARM SYSTEM VERIFICATION REPORT (Subsections A through K) - Formatted for a different jurisdiction
      C2.  DOCUMENTATION (Subsections A through G) - MISSING
      C3.  FIELD DEVICES AND RELATED CIRCUITS - TEST AND INSPECTION (Subsections A through H) - MISSING
      C4.  DATA COMMUNICATION LINK TEST (Subsections A through F) - MISSING
      C5.1  CONTROL UNIT OR TRANSPONDER TEST (Subsections A through JJ) - MISSING
      C5.2  VOICE COMMUNICATION TEST (Subsection A through P) - Not Applicable but must still be included
      C5.3  REQUIRED SYSTEM RESPONSE TIMES (Subsections A through F) - MISSING
      C5.4 CONTROL UNIT OR TRANSPONDER INSPECTION (Subsections A through P) -  MISSING
      C5.5 LARGE SCALE NETWORK SYSTEMS (Subsections A through E) - Not Applicable but must still be included
      C5.6 POWER SUPPLY INSPECTION (Subsections A through G) - MISSING
      C5.7 EMERGENCY POWER SUPPLY TEST AND INSPECTION (Subsection A through U) - MISSING
      C5.8 ANNUNCIATOR AND REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION (Subsection A through N) - Not Applicable but must still be included
      C5.9 ANNUNCIATORS OR SEQUENTIAL DISPLAYS (Subsection A through K) - Not Applicable but must still be included
      C5.10 REMOTE TROUBLE SIGNAL UNIT TEST AND INSPECTION (Subsection A through D) - Not Applicable but must still be included
      C6.1 FIELD DEVICE TESTING - LEGEND AND NOTES - MISSING
      C6.2 INDIVIDUAL DEVICE RECORD - Incomplete
      C6.3 SIGNALLING DEVICE SOUND LEVEL MEASUREMENT - MISSING

    2. The “installed correctly” columns on the individual device test records are marked “YES”, when in fact there are a number of field devices installed INCORRECTLY (i.e. spacing requirements for heat detectors do not comply with CAN/ULC-S524-01).

    3. System is identified as a two stage system.  There are no two stage manual stations installed and no documentation that might suggest this may be an approved design or that the system’s upgrade received a formal review and approval by the local jurisdictional authority.  The test report does not document testing of the GA loop, required automatic transfer functions, or manual acknowledge/cancel.

    4. There are a number of initiating modules (supporting field devices) installed on the data communication loop (DCL) serving the sleeping rooms and common area conventional field devices. These consist of single and dual input modules.  There is no C6.1 “Device Testing - Legend and Notes” and consequently no reference to model number, type, or wiring method.  In addition all field devices (supporting and active) must be individually identified, and VERIFIED (this includes testing for supervisory, ground-fault, correct annunciation and operation).

    5. There are a number of relay modules (supporting field devices) installed on the data communication loop (DCL) serving the various floors of the building.  There is no Appendix C6.1 “Device Testing - Legend and Notes” and consequently no reference to model number, type, or wiring method.  All fire alarm field devices (supporting and active) must be individually identified, and VERIFIED (see item 4).

    6. There are no sensitivity readings recorded on the individual device test record sheets for any of the smoke detectors.

    7. The function of a dedicated water flow relay (for offsite notification of a sprinkler trip) is not listed (or mentioned) on the test report (it was never supplied).  This requirement is articulated in Sentence 3.2.4.7.(2) of BCBC 2006 (NBC 2005).

    8. The DSC PC-2525 security panel utilized to transmit fire alarm signals to the fire signal receiving centre IS NOT ULC Listed for use as a fire alarm communicator as is indicated on the C1 form.

    9. There is inadequate protection of Data Communication Link circuit (not a single DCL isolator was found to be installed).

    10. There are two (2) conventional heat detectors installed on the Data Communications Link circuit without benefit of a connection to a supporting field device.  Activation of these detectors imposes a dead short across the DCL circuit which compromised the loop controller and, in the absence of the required isolation, resulted in a total communications loss with all the terminated field devices.

    11. Audibility levels have not been documented (and likely not performed).

    12. There are no power supply or emergency power supply (battery) test results (likely not even performed).

    14. Specific test and inspection sections that must document the wiring for the project, as well as system response times, and specific testing of the Data Communication Links are missing.  We have grave reservations these were even conducted.

Let’s examine another botched fire alarm Verification.  The technician that performed what is supposed to document a Verification of a complete fire alarm upgrade in a three storey walk-up apartment calls this Commissioning.  I call it A Complete Fraud, and yet the documentation looks to have been accepted by the local authority.

2015 Bogus Verification (Commissioning?) Report posted by Frank Kurz on Scribd

 

Section 15 of ASTTBC’s Practice Guideline provides some good insight into the issue of responsibility, and could easily be adopted into the every-day practice of all building life safety systems service professionals in Canada: 

    “The first duty of care of an ASTTBC Registrant is the protection of the public interest.  Effective application of the ASTTBC Code of Ethics requires information regarding unethical practices and is to be reported to the ASTTBC Practice Review Board (and the local jurisdictional authority).  This requires the combined efforts of FPTs, Owners and Fire Departments.  It is through full vigilance by all those involved that violations of the ASTTBC Act and Regulations, Code of Ethics and Practice Standards can be addressed and the public interest served.”

    Note:  Underlined phrase is added here for clarification.  “CFAA” and “ASTTBC” can easily be interchanged for those Canadian jurisdictions outside of British Columbia (and where a specific ASTTBC Bylaw has not yet been adopted for jurisdictions INSIDE British Columbia).

So, while it’s clear that many technicians have actually been given the responsibility of reporting poor practice, the fact that examples of shoddy inspections like these continue to surface speaks to a certain reticence on the part of the same technicians that I often hear bitching about the state of the industry, as well as to the colossal failure of two key Canadian technician Certification programs.

It is extremely important for any jurisdictional authority to not only understand the technical requirements involved in ensuring a fire alarm system is installed and functions in accordance with the design and CAN/ULC-S524, but to also be able to recognize a properly formatted Verification Appendix “C” report.  In light of the requirements now stipulated in our National Building Code for the Commissioning (Integrated Testing) of a building’s life safety system, it behooves all parties involved to ensure that the documentation attesting to a properly conducted Verification is complete and presents an accurate reflection of this most crucial test a fire alarm system will ever undergo in its lifetime.

The role of an accredited Verifier (recognized by the AHJ) has never been more important at any other time in our industry’s history.  Let’s get down to the business of addressing this.  Let’s not put Public Safety into the hands of companies like Trunk Slammer Safety, Inc.

UPDATE! April 7, 2017

SPECIAL NOTE:  If you are an Authority Having Jurisdiction and would like to receive UNREDACTED copies of the complaint files mentioned below, please email a request to tech@firetechs.net.  Please include your contact information in your email.

Surrey, British Columbia - Formal complaints were filed with both ASTTBC and the CFAA with respect to the Verification performed, and documented by the RFPT involved in the first example provided above.  The bogus Commissioning Report, in the second example, was filed by another technician who is no longer part of ASTTBC’s RFPT programme (thankfully).  ASTTBC assigned an independent reviewer to investigate the alleged violations of both the Practice Guidelines and Code of Ethics suggested by the deficient CAN/ULC-S537-04 documentation that was provided (Complaint Case #16-09).  The investigation report was submitted to the Practice Review Board in March of 2016 and the RFPT was found GUILTY of violating the Code of Ethics and the Practice Guideline.  We received a letter stating that the PRB had imposed censure conditions on the individual responsible, but that he hadn’t yet complied with them.  It is interesting to note that when the CFAA launched an investigation of this technician member’s alleged violations of THEIR Code of Ethics and Conduct, it resulted in a finding that was exactly the OPPOSITE of the ASTTBC PRB’s ruling.  In the formal notice we received, The CFAA’s Executive Director, Steve Clemens, did not provide any explanation other than there were no violations and the matter was considered closed!

And here’s where it gets really interesting!

The RFPT made a formal request for leave to APPEAL the PRB’s ruling to the ASTTBC Council and submitted the results of the CFAA investigation in support.  An ASTTBC appointed Appeal Committee was convened and REVERSED the guilty ruling of the Practice Review Board, dismissing our complaint (and the accompanying censure conditions).  In the formal notification we received from ASTTBC’s Registrar, Charles Joyner, dated March 24, 2017, the reasons for the Appeal Committee’s decision were enumerated in this single sentence:

    “The limited evidence and documentation available to the Appeal Committee as well as the timing and the processing of the complaint were factors that prevented the Appeal Committee from being able to substantiate a violation of the Code of Ethics on the part of Mr. ********.”

When you consider that we have NEVER received any communication from anyone on the Appeal Committee requesting additional information (or inquiring whether any was available), and then juxtapose this against the IDENTICAL document set that was submitted by the VERY SAME RFPT in Case 05-22, the reader will be able to understand what it is we mean when we mention contrary opinions and errors in judgement, in item 3. Standard of Practice, in our Special Report on ASTTBC’s Fire Protection Technician Certification Program:

     “ ... Various interpretations of its (the ASTTBC Practice Guideline) clauses have resulted in inconsistent technician practice as well as a number of contrary opinions and errors in judgment by the Practice Review Board when dealing with complaints involving similar examples of malpractice.  The latter has negatively impacted several technician members who are provided nothing in the way of support throughout this process, and who have been required to pay exorbitant fines that further discourage engagement and positive discourse (one such individual actually resigned from the Programme, abandoning a promising career, which is referenced on Page 8 of – Fire Protection Case Summaries 2013 – Case 13-11).”

In a couple of more recent PRB rulings involving two other RFPTs performing fire alarm system Verifications in the Lower Mainland, the concerns expressed in our Special Report are further supported.  In Case #15-15 and Case #15-17 from ASTTBC’s 2016 Complaint Outcomes, we’ve underlined the IDENTICAL wording used in both, and highlighted in RED the failures we also identified in the complaint filed against the RFPT in Case #16-09:

    “... the failure to follow the CAN/ULC S537 standard for the verification of fire alarm systems, combined with the failure to complete or record device testing, use of the incorrect form, and the incomplete verification report, demonstrated either a fundamental misunderstanding of the requirement for public safety, or a lack of competency in the field of Fire Alarm Verification. ...”

Can anyone reading this update offer us an explanation for the Appeal Committee’s about-face when the facts in our complaint are supported by an independent reviewer’s investigation, the original ruling of the PRB, and the requirements of a Canadian Standard?  In the absence of such an explanation, we have derived three disturbing and irrefutable conclusions:

1.  A successful appeal strategy, for any ASTTBC PRB ruling, involves ensuring there is a LACK OF THE REQUIRED PAPERWORK;

2.  A very select few ASTTBC RFPTs (and CFAA members) are accorded a special status exemption from performing (and documenting) the proper testing and inspection of building life safety systems; and

3.  Public safety in Canada continues to be compromised by some of the very individuals and organizations entrusted with its protection.

It may appear to be an exercise in futility for anyone to even consider filing a formal complaint with ASTTBC (or the CFAA for that matter), but reporting substandard practice is an important and critical imperative if you happen to BE an RFPT.  While it’s unlikely that ASTTBC will ever initiate an investigation involving a violation of Section 15 of the Practice Guideline (mentioned above), I would still advise against rolling that dice and risking your own practice.  C. Y. A.!

Is ASTTBC’s Case #16-09 really closed?  We don’t think so.  There’s a line in the sand that our Educational and Certification Initiatives are going to ensure remains clearly visible.  Which side of it are YOU on?

 

RECOMMENDED ADDITIONAL READING:

Our new series examines the Fire Alarm Verification process in depth.
Our Editorial EXTRA! (April 2015) - The Wolf on the Board!
Our Open Letter to ASTTBC (March 2014 Editorial)
Our September 2014 Editorial
Our August 2014 Editorial
More comments concerning ASTTBC technicians are in in our May 2012 Editorial
ASTTBC Complaint Outcomes (This actually makes for some pretty scary reading.)
CAN/ULC-S536 DO’S AND DON’T’S - Special Reports

 

QUICK LINKS!

AHJ Training Courses are being offered by two (2) Canadian national associations:

  • The Canadian Fire Alarm Association (CFAA) - Please visit their website (link below) for information on one being held in your area.
  • The Fire Technicians Network (FTN) - Feel free to visit our Training Centre for available dates and cities!  To make arrangements for us to present our two day Course Programme in YOUR municipality, please Contact Us for details!

Canadian Fire Alarm Technician Certification:

Fire Protection Equipment Technicians (Extinguisher Service):

Fire Protection Equipment Technicians (British Columbia):

 

INTERESTED IN COMMENTING ON THIS ARTICLE?  QUESTIONS?  GOT A STORY?  SOMETHING OF INTEREST AND/OR NOTE-WORTHY?

Contact Us!

 

The Fire Technicians Network

+1 (888) 340-3473

“We are not a professional union, but together, we are a union of professionals!”

Social MediaFTN Twitter FeedFTN Facebook FeedFTN LinkedIN FeedTechnical RSS FeedSkype for Business

What we’re all about!
We are not affiliated with ASTTBC, CFAA, CANASA, NFPA, NAFED, or NICET (although we encourage you to explore and objectively evaluate the benefits associated with supporting their individual efforts).  Membership in the Fire Technicians Network is entirely voluntary.  Are you up to the challenge of demonstrating your commitment to public safety and the highest standard of professional practice?

Social MediaFTN Twitter FeedFTN Facebook FeedFTN LinkedIN FeedTechnical RSS FeedSkype for Business

Copyright © 2007 - 2022 The Fire Technicians Network.  All Rights Reserved