Tech-Tools
|
|
|||||||||||||||||||||||||||
More information regarding SignaLink Fire-Link® II can be found at www.signalink.com. We recommend that you take the time to review our SPECIAL REPORT from which this guide has been produced. NOTE: Items in RED BOXES all reference requirements stipulated in CAN/ULC-S524-06 (current Fire Alarm Installation Standard referenced by NBC 2010) or NBC 2010, and will result in a FAILED Verification Appendix “C” report (CAN/ULC-S537-04) and create additional issues in the ANNUAL test report (CAN/ULC-S536-04) if the equipment is installed as a PRIMARY signalling means. In addition anyone with an existing home automation system that uses power-line technology (X-10) may create problems for the Fire-Link® II System. We have elected to include an isolator in our example of an in-suite buzzer installation as this provides maximum protection of the in-suite signalling circuit. This is a “best case” scenario (also referred to as “good engineering practice”). You can also download the PDF of the Application Guide!
CODE AND STANDARD REFERENCES: CAN/ULC-S524-06 (Standard for Installation of Fire Alarm Systems) Clause 5.4.3.1: “Where silencing means are separately installed or incorporated in the audible signal device, the silencing means shall be clearly identified and located not less than 1200 mm and not more than 1400 mm above the finished floor level measured from the centre of the silencing means.” Clause 3.3.1.5: “Except as noted in Clause 3.3.1.6, each circuit of a fire alarm system shall be installed such that open circuit faults or ground faults shall not interfere with the operation of other circuits of the fire alarm system, and such faults shall initiate a trouble signal. Note: In conventional two-stage systems, input circuits for first stage and second stage shall not share conductors.” Clause 4.2.7: “Where a data communication link utilizing active field devices or supporting field devices serves more than one National Building Code of Canada required fire alarm zone, a fault within one fire alarm zone shall not prevent the normal operation of other input or output field devices in another fire alarm zone, except as noted in Clause 4.2.8. Note: See also Clause 3.3.1.9” NBC 2010 (British Columbia Building Code 2012) Clause 3.2.4.19(9): “In a building or part thereof classified as a residential or care occupancy, separate circuits shall be provided for audible signal devices on each floor area, and audible signal devices within dwelling units or suites of residential or care occupancy shall be wired on separate signal circuits from those not within dwelling units or suits of residential or care occupancy. (See A-3.2.4.19.(8) in Appendix A.)” Clause 3.2.7.8(3): “The emergency power supply required by Sentence (1) shall be capable of providing supervisory power for not less than 24 h, and immediately following that period, emergency power under full load for not less than - 2 h for building within the scope of Subsection 3.2.6, (See Appendix A.)”
COMMENTS: The fire alarm SYSTEM must be installed in accordance with CAN/ULC-S524-06 and NBC 2010. You could use the Signalink Fire-Link® II equipment in an upgrade to supplement the in-suite signalling appliances required by NBC 2010 to ensure you achieve the 75dBA at the pillow. You would still be required to provide installation of signalling appliances within the suite, connected, isolated, and supervised by an output circuit serving the suites on that floor (or within the specific floor area) in order to achieve compliance with NBC 2010. The Signalink equipment may well represent a viable solution to the problem of achieving the required sound pressure levels when retrofitting signalling appliances in older buildings. Its use, however, must still be carefully considered, strictly monitored, and regulated to ensure we’re not compromising the safety of residents or recommending an alternative that may, in fact, compromise the Building Code and the Installation Standard. In older apartment buildings which may employ aluminum or other substandard wiring components, it is even more important, in our view, to carefully examine any formal submission in which the use of the Signalink equipment is proposed. Keep in mind that if the fire is electrical in nature (the single most likely cause in older buildings), the ability of the Signalink system to notify occupants may become impaired (or completely compromised) because it’s utilizing that same wiring that could have sparked the fire in the first place in order to transmit the alarm signals.
The manufacturer’s referenced “commissioning test” is generated through the Fire-Link® II system configuration software. While a “before” and “after” comparison is listed as an acceptable alternative to performing a full Verification in Section 6 (entitled “System Modifications”) of CAN/ULC-S537-04, this is NOT, in our opinion, a correct application of Clause 6.11 when referencing a NEW INSTALLATION of a signalling controller (and associated devices). CAN/ULC-S537-04 (Standard for Verification of Fire Alarm Systems) Clause 6.11 states: “Software modifications shall be tested by one of the following methods: A Reverifying all system functions that could be affected by the modifications with the exception of wiring supervision; or B A comparison of the ‘before’ and ‘after software utilizing mediums such as a printout or compare program.” Clause 6.7 states: “Where a control unit or transponder is added to an existing system, the control unit or transponder and all new and existing field devices connected to it shall be verified in accordance with this Standard. (Refer to Clause 6.10)” Clause 6.10 states: “Modifications to a control unit or transponder and those circuits affected shall require the modifications to be verified in accordance with Subsection 4, Verification Procedure – Control Unit and Transponders.”
DISCLAIMER: We wish to assert that it is NOT our intention to suggest that the SignaLink Fire-Link® II System is not suitable in a RETROFIT application as a supplemental signalling component. We are also not denigrating, vilifying, or impugning the technology, the Mircom Group of Companies, their management, employees, or authorized distributors through the publication of this document. This article is the carefully considered opinion of the author, and its sole purpose is to provide a CANADIAN Code and Standard referenced interpretation of the equipment’s application so that it is not incorrectly utilized where a current Code compliant upgrade is being considered. More information regarding SignaLink Fire-Link® II can be found at www.signalink.com and in our SPECIAL REPORT. Questions or comments about this article can be directed to: tech@firetechs.net, the CONTACT US page, or by calling 1-888-340-3473 (toll free in North America). Frank Kurz
ADDITIONAL RESOURCES: Fire Alarm Verification Appendix “C” & Fire Alarm Inspection Appendix “E” Forms Questions? Comments? Contact Us! |
||||||||||||||||||||||||||||
|
|
+1 (888) 340-3473
“We are not a professional union, but together, we are a union of professionals!”
What we’re all about!
We are not affiliated with ASTTBC, CFAA, CANASA, NFPA, NAFED, or NICET (although we encourage you to explore and objectively evaluate the benefits associated with supporting their individual efforts). Membership in the Fire Technicians Network is entirely voluntary. Are you up to the challenge of demonstrating your commitment to public safety and the highest standard of professional practice?
Copyright © 2007 - 2020 The Fire Technicians Network. All Rights Reserved