Despite the reference to CAN/ULC-S537-04 and the date encoded at the upper left of the document (June 2004), the format of the first page of the report (the C1 - Report face page) in no way resembles either of the two acceptable Appendix "C" versions. What's missing? It doesn't identify the Verification that was actually performed (detailed in Items C through G), nor does it make any reference to the installed system meeting the requirements of CAN/ULC-S524 and the design (Item H). It is, after all based on the 1997 version of the Standard which, incidentally, was NOT the published version referenced in BCBC 2006 (the Building Code in effect at the time). CAN/ULC-S537-04 was. Without even having to list the other required Items, or turning past the first page of the report, the criteria for rejection we mentioned in Part One has already been clearly established.
Let's review another form for a fire alarm installation in another British Columbia jurisdiction, which will help highlight what we've already discussed regarding a properly formatted document and the criteria for rejection, and which will allow us to smoothly segue into two important (and frequently abused) Sections of the Appendix "C" Report form - C6.1 - Field Device Testing - Legend (missing in this example), and C6.2 - Individual Device Record:
Bogus CAN/ULC-S537-04 Fire Alarm Verification Appendix "C" posted by Frank Kurz on Scribd
In this example of a failed Verification (which is also the focus of our October 2016 Editorial), the technician has elected to submit the City of Vancouver's modified CAN/ULC-S537-04 Appendix C1 - Report first page followed by five pages of a radically modified (but largely incomplete) C6.2 - Individual Device Record. The report is supposed to document the Verification performed on an installation of a new, fully addressable Mircom FX-2000 fire alarm control. Several of the required testing and inspection parameters have not been properly documented. They include smoke detector sensitivity scores, proper annunciation, and ground fault. What this report truly represents is an outstanding example of the perfect storm of failure criteria. Unfortunately, this report's format, and other equally questionable variations there-of, is actually quite typical of what I see employed in many jurisdictions across the country.
C6.1 - Field Device Testing - LEGEND and Notes
What is it?
It documents the type and model number of every fire alarm field device installed on a system. It provides the technician with the means to record the testing criteria of the smoke detectors (including their sensitivity ranges and their testing means) and lists ancillary devices which may be installed and connected to the system. It also provides a handy cross-reference (or legend) for the abbreviations used in C6.2 - The Individual Device Test Record.
What exactly IS a fire alarm field device?
The Standard (CAN/ULC-S537-13) defines it as:
“A device located remotely from, but connected electrically to, the control unit or transponder to provide status change information (e.g. fire alarm detection or signalling).”
The list of field devices can be categorized into the following groups:
- Active Field Device
- Supporting Field Device
- Conventional Field Device
- Audible Signal Device
- Supervisory Device
- Visible Signalling Device
- Fire Detectors
And subgroups that include (but certainly aren't limited to):
- smoke detectors
- duct smoke detectors
- beam smoke detectors
- manual stations
- heat detectors
- combination type detectors
- fault isolation modules
- suite isolator devices
- end-of-line devices
- power isolation modules
- flame detectors
- sprinkler flow switches
- sprinkler valve indicating switches
- sprinkler supervisory devices (low air, low temperature, etc.)
- bells, horns, buzzers, speakers
- remote alarm indicators
- addressable initiating circuit modules
- addressable relay modules
- addressable output modules
Do you have to list every installed and connected field device in a system in Section C6.1?
Most definitely, YES! You must identify them by both type and model number.
An example could be something as simple as a manual station. Is the type "single" or "double action"? Is it addressable or conventional? What's the model number? This information could prompt the qualified individual to question whether the contractor should be installing the cheaper single action stations in a building which predominately employs double action types. It should also suggest that the qualified individual check to ensure that all the installed manual stations in the project operate and reset the same way.
In an application involving linear heat detection in a cooler, it would be incumbent on the qualified individual to ensure that the model number of the ULC Listed cable being used has been properly tested (and certified) for the anticipated environment it's going to be deployed in to monitor.
Are the smoke detectors listed on the C6.1 form compatible with the control panel to which they're connected? Listing the model number of each individual smoke detector (and base) should prompt the qualified individual to check the compatibility chart for the specific version of control panel, as published by the manufacturer.
And in a residential type installation, where two distinct types of suite signal isolators currently ULC Listed for use with a fire alarm system in Canada are available, only one is actually acceptable. The unit illustrated below most definitely IS NOT!
Identifying the model number is of paramount importance and will help establish the criteria for acceptance or rejection of any field device by the qualified individual. It should be noted that the above examples ALL require conformance with specific testing parameters in the referenced Standard as well (something we'll cover in future installments in this series) before you can check off any field in C6.2 - The Individual Device Record.
Which actually brings up another important point. Designers MUST ensure that the Verification Agency they know will be engaged to perform this all important test, performs a few site visits during the course of any fire alarm installation (or modification) so that any deficiencies can be identified (and corrected) before they involve expensive alterations which might delay the project's completion (and raise the ire of the Owner).
Engineers and Designers take note: Make at least two site visits, by an AHJ approved Verification Agency, part of YOUR design specification!
C6.2 - Individual Device Record
What is it?
Quite simply, it documents the testing and inspection of each individual field device.
Is a supporting field device (one that's monitoring the status of a sprinkler flow switch, for instance) supposed to be individually listed?
Most emphatically YES! You must also detail its location and performance.
What must be documented?
Besides the zone, module or circuit number, the form documents the correct installation of each itemized device, its location, operation, electrical supervision, and other pertinent performance parameters.
Incorrect smoke detector installation!
On some field devices (smoke detectors, sprinkler flow switches, and end-of-line devices, for instance), these other parameters require some special additional comments. For smoke detectors, the approved individual must list the sensitivity level, for sprinkler flow switches, the activation delay must be recorded.
When an AHJ can identify that a fire alarm system employs addressable field devices and no reference to isolator modules is made on either the C6.1 or C6.2 forms, this should automatically raise two questions:
Are they even installed? And if they are, were they properly tested?
Note: You would have to determine the installation methodology utilized (which should be detailed in the other sections of the Appendix "C") to make a determination as to whether-or-not they're actually required. If you're uncertain, or it's not clear enough on the report (which can also be considered another criteria for rejection), ASK!
When a fire alarm system employs conventionally wired circuits (or zones), the locations and testing of each end-of-line resistor (and relay) must be detailed. And since this important field device is the LAST DEVICE in a circuit, the voltage measurement across the device must be recorded here as well. How else can the approved individual determine that the voltage drop on the circuit is within the acceptable limits as specified by the manufacturer?
Proper connection of the field wiring at all system termination points must be checked!
It goes without saying (but since no one else is, I may as well), that BLANK spaces on the C6.2 form that appear in the columns next to a listed device DO NOT automatically mean "Not Applicable". For anyone engaged in reviewing a C6.2 form, BLANKS should be carefully examined and may actually qualify as another of your criteria for rejection.
The Verification remains one of the most crucial test and inspections a fire alarm system will undergo in its lifetime. The documentation that details the installation must be complete and accurate. Mistakes, deliberate omissions, and incomplete sections are all important indicators that the individual conducting the inspection may NOT meet the knowledge requirement, or (at the very worst) lacks the professional integrity an AHJ must demand of anyone they approve.
It is also incumbent on the personnel engaged in performing this vital service that they understand that failure is not an option and will not be tolerated!
We'll be exploring additional sections of the Standard in upcoming installments. Stay tuned!
RECOMMENDED ADDITIONAL READING:
Our Editorial EXTRA! (April 2015) - The Wolf on the Board! Our Open Letter to ASTTBC (March 2014 Editorial) Our September 2014 Editorial Our August 2014 Editorial More comments concerning ASTTBC technicians are in in our May 2012 Editorial ASTTBC Complaint Outcomes (This actually makes for some pretty scary reading.) CAN/ULC-S536 DO’S AND DON’T’S - Special Reports
QUICK LINKS!
AHJ Training Courses are being offered by two (2) Canadian national associations:
- The Canadian Fire Alarm Association (CFAA) - Please visit their website (link below) for information on one being held in your area.
- The Fire Technicians Network (FTN) - Feel free to visit our Training Centre for available dates and cities! To make arrangements for us to present our two day Course Programme in YOUR municipality, please Contact Us for details!
Canadian Fire Alarm Technician Certification:
Fire Protection Equipment Technicians (Extinguisher Service):
Fire Protection Equipment Technicians (British Columbia):
INTERESTED IN COMMENTING ON THIS ARTICLE? QUESTIONS? GOT A STORY? SOMETHING OF INTEREST AND/OR NOTE-WORTHY?
Contact Us!
|