Firetechs Logo

 

Kidde Bulletins
& Technical Notes
Your IP Address is:
38.107.191.102

Kidde

Smoke Alarm RECALL (July 2009):
Kidde has announced a voluntary recall of their Model PI 2000CA dual sensor smoke alarms. Apparently an electro-static discharge can adversely affect the detector. Affected units were manufactured between January 1, 2009 and May 4, 2009. You can view all the details (and what you must do) here.

Fire Extinguisher RECALL (March 2009):
Affects Kidde XL Fire Extinguishers manufactured betwen October 2007 and April 2008 with model numbers FX210R and E-340-3. The extinguisher can lose pressure which could put the end-user at risk. Consumers are urged to check the pressure gauge to ensure it is still in the "green" range. They are also urged to contact Kidde Customer Support to verify that their extinguisher serial number does not fall within the range of this recall. The Customer Support number is listed below.

Commercial Fire Extinguisher RECALL (July 2005):
Affects Kidde 10 lb. industrial dry chemical fire extinguishers with black plastic Zytel® nylon valves in steel cylinders manufactured between 1991 and 2000. The nylon valves on these extinguishers can separate from the steel cylinder during the 6-year recharge service or shortly afterwards creating a safety hazard to fire extinguisher service personnel and consumers. DO NOT SERVICE THESE EXTINGUISHERS! More details concerning this recall and the replacement program can be found here.

Firex Smoke Alarm/Carbon Monoxide Detector RECALL:
Affects Maple Chase Company products that include Firex branded model 10000 and 12000 series smoke alarms and carbon monoxide detectors. You may view additional information here.

Chemtronics 500 & 600 series Heat Detectors BULLETIN:
Kidde/Fenwal have issued a bulletin regarding the terminal strips located on the bottom of the affected detectors. Apparently some units were manufactured with "out of tolerance" rivets which may cause the entire terminal assembly to separate from the body of the detector. On supervised fire alarm circuits this would NOT cause a "trouble" signal as the terminal strip still provides a positive connection, however, the unit will fail to register an alarm condition. You can view additional information (including the corrective action you must take) here.


Manufacturer Technical Support Numbers

Customer Support: 1-888-345-4407

 

 


Smoke Detector Cross-Listing Information

ULC Compatibility Index

You'll be prompted to either "save as" or "open" a Microsoft® Excel document.
Please read our Terms of Use!

Note: It is important to note that the panel manufacturer (in Canada) must list compatible smoke detectors. Using a non-compliant smoke detector with any ULC® Listed fire alarm control invalidates its certification and could place the building occupants at risk. If you have questions regarding compatibility of a particular smoke detector (not shown on the list), please contact the manufacturer.


WWW.FIRETECHS.NET Contact Information

24/7

Telephone: 604-468-8324 (TECH)

North America Toll Free: 1-888-340-3473 (FIRE)

email: tech@firetechs.net

 

 
Copyright © 2008 - 2010 by The Fire Technicans Network
All Rights Reserved
E&OE