Fire Pump Controller RECALL:
Affects pressure transmitters installed in Diesel fire pump controllers manufactured between September 1, 2007 and August 8, 2008 and in electric fire pump controllers manufactured between June 11, 2007 and August 8, 2008. Voltage transients may have adversely affected the GEMs 3100 series pressure transmitter which may cause it to read the incorrect pressure and fail to initiate the start sequence when required. For more information regarding product identification and installation instructions, please click here.
|